AD16-22/22
Indicator Lamp Technical Quick Reference
AD16 series Φ22 mm panel-mount signal lamps (indicator lamps, power indicator lamps, sound-and-light signal lamps). This quick-reference sheet consolidates voltage ratings, AC/DC compatibility, color semantics and application pairing with adjacent equipment into a single page, so the correct part number can be confirmed in 30 seconds, before you order.
Reading the part number
AD16-22/22 is a shortened form widely used by sellers. Break the part number apart and each position tells you one thing: where it mounts, what shape it is, what color it is, what voltage it takes, and what protection level it carries.
Applicable to power, telecommunications, machine-tool, marine, textile, printing and rail-transit circuits in AC 50 Hz (or 60 Hz) up to 500 V and AC/DC up to 500 V, used as signal indication, warning indication and accident signaling wherever light is used as the means of indication.
- High-brightness single-colour LED chips — true colour, low power draw
- Lens in high-strength polycarbonate — impact resistant, good insulation
- Built-in screw terminals for a high safety factor
- Text and symbols can be laser-etched or screen-printed
- Nut-locking panel mount, suits 1–6 mm panel thickness
- AC and AC/DC versions have different internal circuits — not interchangeable in the same housing
- Marketplace listings often state color only, omitting voltage
- The IP40 base type is unsuitable for outdoor or wash-down duty
- Standard types must not be used in explosive gas atmospheres
- Mis-wiring an AC bi-color lamp destroys it
Available voltages · Is AC/DC universal?
Straight answer: the low and mid range (6–48 V) is mostly available as AC/DC universal; above 110 V you must confirm whether the part is universal or AC-only. Universal never means "any voltage will do".
| Voltage code | Nominal voltage | Supply type | Dropper type | Rated current | Frequency | Typical use |
|---|---|---|---|---|---|---|
| 21 | AC/DC 6 V | Universal | ResistiveAccepts 6 V DC or 6 V mains AC | 15 / 25 / 35 mAVaries with color | 50–60 Hz | Low-voltage control circuits, small sensors, PLC signals |
| 22 | 12 V | Universal | Resistive | 15 mA | 50–60 Hz | Automotive/instrument, 24 V system applications, relay signals |
| 23 | 24 V | Universal | Resistive | 15 mA | 50–60 Hz | Most common: PLC, VFD, machine tools, EV-charger control signals |
| 24 | 36 V | Universal | Resistive | 15 mA | 50–60 Hz | Certain machine tools and mining equipment control circuits |
| 25 | 48 V | Universal | Resistive | 15 mA | 50–60 Hz | Telecom power, PV combiner boxes, 48 V DC systems |
| 26 | 110 V | Universal | Resistive | 15 mA | 50–60 Hz | 110 V industrial network status indication |
| 27 | 127 V | Universal | Resistive | 15 mA | 50–60 Hz | Mining and some industrial network voltages |
| 28 | AC/DC 220 V | Universal | ResistiveHousing temperature rise exceeds the AC type above 110 V | 10 mA | 50–60 Hz | 220 V distribution panel indication, covers both DC and AC sites |
| 29 | 380 V | FD dedicated | Capacitor cabinet discharge type | 10 mA | 50–60 Hz | Capacitor cabinet door indication, live-bus indication inside |
| 30 | AC 500 V | AC only | Capacitive | 8 mA | 50–60 Hz | HV switchgear phase sequence and live indication |
| 31 | AC 220 V | AC only | Capacitive | 15 mA | 50–60 Hz | Mains 220 V motor and circuit running indication (lowest cost) |
| 32 | AC 380 V | AC only | Capacitive | 18 mA | 50–60 Hz | Three-phase 380 V motor running indication, main switchgear panels |
Universality has conditions
"AC/DC universal" means that at the same nominal voltage the lamp lights on both AC and DC, which covers 6–48 V and part of the 110/220 V range. It does not mean a 220 V AC lamp can run on 24 V, or that a 24 V lamp can run on 220 V.
Two different dropper circuits
The AC/DC type uses a resistive dropper, the AC type a capacitive one. At the same nominal voltage the circuit, housing and heat output all differ, so you cannot "keep the housing and swap the lamp core". The AC type works only at 50/60 Hz — other frequencies will destroy it.
Configuring DC systems
Where the equipment runs on a DC bus (24 V / 48 V / 110 V DC), choose an AC/DC universal type rated for DC, so one lamp serves both the DC control circuit and mains testing during maintenance. AC tolerates ± 20 % voltage fluctuation (above 110 V).
Available colors · Where each is used
Click any color card and the lamp above switches to that color in real time. Color semantics follow the IEC 60073 / GB/T 4025 conventions, combined with how electrical practice actually reads them on site.
- Equipment fault and alarm indication
- Status lamp after the emergency stop is pressed
- "Live / energized" warning on distribution panels
- Abnormal indication on fire and safety circuits
- Motor, fan and pump running indication
- Power healthy, system ready, start permitted
- Safety circuit closed, access control and earthing healthy
- Charger connected and idle, UPS on mains
- Standby, ready, remote or manual mode
- Low level, low pressure, filter due for change
- Parameter out of limits, temperature rise warning
- UPS on bypass, running on battery
- Program running, automatic/manual mode indication
- VFD running, motor regeneration / feedback state
- Charging, link online, data uploading
- Position indicator (isolator open/closed, earthing)
- Panel interior lighting, general panel illumination
- Circuit live, power available indication
- Circuit numbering in multi-circuit panels
- Open/closed position indication (with D/N/G codes)
- Vendor-defined states (e.g. "filling", "changing material")
- Dedicated marking of a special process step
- Alignment with an existing customer HMI color standard
Application pairing with adjacent equipment
The same lamp can demand a different color and voltage for the same position in different industries. Below, the common equipment is matched line by line.
Switchgear & distribution
switchgear- Incoming line / busbar energized warningHazard marking — do not touchAC 220 V · red · steady
- HV panel phase sequence / live indicationThe 500 V version connects directly across the main busAC 380–500 V · red · dedicated
- Earthing switch closedPosition indicator with D/N/G codesAC 220 V · green
- Panel interior lightingGeneral illumination, carries no statusAC/DC 220 V · white
- SPD degradation monitoringAuxiliary signalAC/DC 24 V · blue
Machine tools & automation
machine tool- Spindle / motor runningThe canonical "green = running"AC 380 V / 24 V · green
- Alarm / after emergency-stop resetRed flashing paired with a buzzer24 V · red · sound-and-light
- Servo / system standbyNeither faulted nor running24 V · yellow
- Automatic mode / program executingSpecial-function state24 V · blue
- Low lubrication pressure / low coolant levelWarning, not yet an alarm24 V · yellow
Renewables & charging
energy- Charging gun connected / readyCharging may begin24 V DC · green
- Charging in progressProcess state uses the information color24 V DC · blue
- Insulation fault / comms lossRequires a shutdown24 V DC · red · flashing
- PV inverter grid-tied and runningGrid-tied = normal48 V / 220 V · green
- Storage SOC low / on battery bypassAlarming but still running48 V DC · yellow
Buildings & HVAC
hvac- Pump / fan runningMotor running indicationAC 220 V / 380 V · green
- Pump fault / phase lossShutdown / fault class — shown in red24 V · red
- Low level / pressure warningYellow first, red later24 V · yellow
- Elevator running / leveledRequired by fire code24 V DC · green
- Maintenance mode / door openPersonnel are intervening24 V DC · yellow · flashing
Transport & marine
transport- Train battery supplyDC systemDC 110 V · blue
- Platform / vehicle doors closedMovement permitted24 V DC · green
- Main engine running / steering gear failureMarine engine-room conventionAC 220 V / 24 V · red
- Engine-room alarmPaired with the buzzer24 V · yellow · sound-and-light
Chemicals & electrolysis
process- Rectifier unit runningHigh-current output working stateAC 380 V · green
- Polarization voltage / cell voltage displayA separate information channelAC 380 V · blue
- Rectifier fault shutdownShutdown class of red24 V · red
- Circulation / cooling pump on standbyTransitional state24 V · yellow
Data center & logistics
datacenter- UPS on mainsDual incoming supply indicationAC 220 V · green
- UPS on bypass / on batteryDegraded operation24 V · yellow
- Server / air conditioner runningRunning state24 V · green
- AGV charging / link onlineProcess and information24 V DC · blue
- Forklift / AGV battery lowTime to swap the battery24 V DC · yellow
Fire & safety
fire & safety- Fire power supply healthyA color fixed by regulationAC 220 V · green
- Fire alarm control panel alarmSound and light together24 V · red · sound-and-light
- Manual call point pressed / hydrant pressure lowSignal for human intervention24 V · yellow
- Safety circuit closedOperation permitted24 V · green
Selection in six steps
Click through each step to confirm the key points; the progress bar records what you have already verified. Once all are ticked, the part number is essentially settled.
Confirm installation conditionsPanel cut-out and thickness
Standard cut-out Φ22 mm (catalog tolerance Φ22.2 +0.5/−0.0 mm); reducing rings cover Φ25 mm / Φ30 mm. Typically suits 1–6 mm panels, with a threaded barrel and lock nut. Tighten to 1.5–2.0 N·m — overtightening can crack the plastic housing.
Determine the supplyAC or DC bus
First establish whether the circuit being indicated is mains AC or a DC bus, then note the voltage. For 6–48 V prefer an AC/DC universal type — one lamp works on the DC control circuit and on mains for testing. For 220 V/380 V main circuits prefer the AC-only type, to avoid the higher housing temperature rise of a resistive type.
Match color semanticsKeep consistent with the other lamps on the panel
Color meaning must be consistent within one system: green = normal/running, red = fault/stop, yellow = warning/standby, blue = special function, white = neutral/energized. If another color is already taken on the panel, confirm with the site whether the existing convention is kept before deciding on orange or a bi-color lamp.
Choose the lamp typeSteady / flashing / bi-color / sound-and-light / position
A steady type is enough for a single state. For alarms that must grab attention use the flashing type (S) or sound-and-light type (SM). To distinguish two or three states use bi-color (SS) or tri-color lamps. For switchgear position indication use the P series with G/D/N codes. In noisy areas prefer sound-and-light — buzzer output reaches 80 dB at 10 cm.
Verify protection levelDriven by the installation environment
The base head is IP40 and suits indoor control panels. Outdoors, in dust, where wash-down is needed, or mounted outside a machine, choose the P code for IP65 or order the IP67 version; some round heads reach IP65 directly. Standard types are not permitted in hazardous areas — select an Ex-certified product.
Check electrical margin and wiringThe last mile
AC tolerates ± 20 % voltage fluctuation (above 110 V). On the DC side allow 15–20 % margin so a bus dip is not misread as a lamp failure. Wire with screw terminals, 0.5–2.5 mm²; prefer the plug-in connector (2.5 × 0.8 mm) to soldering — if soldering is unavoidable, use an iron below 30 W for no more than 3 seconds, and do not stress the terminal.
Main technical specifications
Compiled from manufacturer catalogs and CCC certification documents. Values differ slightly between manufacturers — confirm against the sample supplied with the goods before ordering.
Pre-order checklist
A fully specified order avoids almost every "it arrived wrong" rework. Tick the items before sending the requisition.