AC Contactor LC1: NO vs NC Difference, Model Decoding, Use Cases & Wiring
ORIGINAL · LOW-VOLTAGE ELECTRICAL TECH NOTES

AC Contactor LC1: What Exactly Separates NO from NC? How to Read the Model, Where to Use It, and How to Wire It

Schneider Electric's LC1 (TeSys) is the most common AC contactor on the industrial floor. This article covers in one pass the real difference between Normally Open (NO) and Normally Closed (NC) contacts, what every letter and digit in the model number means, typical application scenarios, and how to wire the main and control circuits — with an interactive demo and wiring diagrams. After reading, you can select and wire it on your own.

NO vs NCLC1D Model DecodingSelf-Hold / Interlock WiringReversing ControlSelection Cheat-Sheet
01

What is LC1 — know the family first

"LC1" is the model prefix of Schneider Electric's (formerly Telemecanique) TeSys-series AC contactors — found everywhere in factories and switchgear. It uses a small current (the coil) to switch a large current (the main contacts), enabling remote motor start/stop, reversing, star-delta reduced-voltage starting, and general load switching.

Within the same LC1 family there are different series suffixes. Identify the family first, then you won't buy the wrong one:

SeriesCurrent rangePositioning & featuresCommon codes
LC1D (TeSys D)9–150 AGeneral-purpose workhorse covering most motors (4–75 kW); expandable aux contacts, mechanical interlock, surge suppressor modulesLC1D09…LC1D150
LC1F (TeSys F)115–800 AHeavy-duty: Ag-graphite main contacts, double-break arc extinction, withstands frequent AC-4 reversing/jogging, longer lifeLC1F115…LC1F780
LC1N (EasyPact D3N)6–95 AEconomy, high cost-performance; fans/pumps/lighting/small automationLC1N06…LC1N95
LC1G (TeSys Giga)185–2600 AUltra-high power; AC/DC wide-voltage coils (BEE/EHE/KUE/LSE)LC1G185…
LC2 / LC3—LC2 = reversing contactor assembly (mechanically interlocked F/R); LC3 = star-delta contactor assemblyLC2D, LC3D
One-line memoryWhen people say "LC1 contactor", 90% means the LC1D branch; this article focuses on LC1D, but the other series follow the same naming logic.
02

Core difference: Normally Open (NO) vs Normally Closed (NC)

This is the heart of the article. The "closed" (开闭) usually refers to Normally Closed (NC) — many electricians verbally say "closed contact" versus "open contact". The single criterion that separates them is the contact state when the coil is de-energized (no power):

NO (Normally Open)OPEN when coil de-energized, CLOSED when energized. Like a switch that "closes only when pressed".
NC (Normally Closed)CLOSED when coil de-energized, OPEN when energized. Like a switch that "is closed by default, opens once energized".

▶ Try it yourself (click to simulate coil energization)

Click the button to energize / de-energize the electromagnetic coil and watch the two contacts move in opposite directions: the NO "closes only when pulled in", the NC "opens when pulled in".

Coil A1·A2 1/3/5 2/4/6
Normally Open (NO)
Coil de-energized: OPEN ✗
Coil A1·A2 21 22
Normally Closed (NC)
Coil de-energized: CLOSED ✓

▶ One table for all the differences

ItemNormally Open (NO)Normally Closed (NC)
Default (coil de-energized) stateOpen (no conduction)Closed (conducting)
Coil energized stateClosed (conducting)Open (no conduction)
Electrical symbolTwo broken lines (with a gap)A slash across the contact (indicates normally closed)
Terminal numberingEnding in 13-14, 23-24, 33-34 (even 4 = NO)Ending in 11-12, 21-22, 31-32 (even 2 = NC)
Position on contactorMain contacts (all NO); some aux also NOOnly on auxiliary contacts
Typical useStart, self-hold (seal-in), run feedback, indicatorStop, electrical interlock, protective interlock, fault alarm, safety circuit
Terminal numbering rulePer IEC: terminals ending in 1-2 are NC, ending in 3-4 are NO; odd numbers (1/3/5…) are common terminals, even (2/4/6…) are outgoing. E.g., 21-22 is NC, 13-14 is NO.

▶ Main contacts vs auxiliary contacts

  • Main contacts (1/L1-2/T1, 3/L2-4/T2, 5/L3-6/T3): all 3 poles are Normally Open. They carry the motor's large current (a few amps up to over a hundred) and sit under the arc chute. When the coil is energized, all three close and the motor runs; when de-energized, all open.
  • Auxiliary contacts (13-14 NO, 21-22 NC): very small capacity (~10 A thermal), used only in the control circuit. A standard 3-pole LC1D already builds in 1NO + 1NC; when insufficient, snap the LA1DN expansion module (2NO / 2NC / 1NO+1NC) onto the top.
Common pitfallMain contacts are always NO — don't expect to use them as "conducting by default". For logic that must "conduct when de-energized and open when energized", you must use an auxiliary NC contact.
03

How to read the LC1 model (decode it)

Take the most common LC1D0910M7C (or the newer LC1D09M7C) and break down every segment:

SegmentMeaningNotes
LC1Contactor productSchneider TeSys AC contactor prefix (DC is LP1)
1Structure type1 = single; 2 = reversing assembly (F/R); 3 = star-delta assembly
DSeriesD = TeSys D (general); F = TeSys F (heavy); N = EasyPact (economy); G = Giga (ultra)
09Current ratingMax operating current at AC-3, 440 V; 09 = 9 A
10Aux contact code (legacy)Older: 10 = 1 NO, 01 = 1 NC; current 3-pole standard builds in 1NO+1NC, segment often omitted
M7Coil voltage + frequencyM = 220 V AC; 7 = 50/60 Hz universal (also 5 = 50 Hz, 6 = 60 Hz, D = DC coil, L = low-consumption DC)
COriginC = domestic (China); omitted = imported
Add "00" above 115 AFor the LC1D115–170 range, you must insert 00 after the current, e.g., LC1D11500M7C; otherwise the model is invalid.

▶ Current rating ↔ motor power cheat-sheet (AC-3, 380/400 V)

Current (A)ModelMotor powerTypical load
9LC1D094 kWSmall pumps, small fans
12LC1D125.5 kWConveyors, machine-tool aux
18LC1D187.5 kWCompressors, grinders
25LC1D2511 kWMid-size fans/pumps workhorse
32LC1D3215 kWAir compressors, hoists
38 / 40LC1D38 / LC1D4018.5 kWCrushers, large pumps
50LC1D5022 kWLarge fans, injection machines
65LC1D6530 kWProduction-line main drive
80LC1D8037 kWCentral AC, chillers
95LC1D9545 kWLarge pump stations, refrigeration
115 / 150LC1D115 / LC1D15055 / 75 kWHeavy large motors (above 75 kW, go LC1F)
Size down, not to the maxThe rated current is the AC-3 upper limit. For motors with frequent reversing (>30 jogs/hour), heavy long-acceleration starts (centrifuges, crushers), or cabinets running >40 °C long-term, step DOWN one size — e.g., an 11 kW motor goes from LC1D25 to LC1D32; contact life differs a lot while the price gap is small.

▶ Coil voltage codes (most often ordered wrong)

CodeAC coil voltageTypical scenario
B724 V ACFrom a safety isolating transformer
F7110 V ACImported / legacy equipment control
M7220 V ACMost common in domestic equipment
P7230 V ACEuro-standard equipment
Q7380 V ACDirectly from two mains phases

Common DC coils: BD = 24 V DC, FD = 110 V DC, MD = 220 V DC; wide-voltage low-consumption coils use L or the Green series BEE/EHE/KUE/LSE. When a PLC transistor/relay output drives a small contactor directly, prefer 24 V DC (e.g., LC1D09BD) — but note that large DC coils may need an interposing relay.

▶ How to tell apart from the physical unit

  • Read the side nameplate: model, current rating, and coil code (e.g., M7) are printed on the white side label — copy it when replacing; don't just remember "0910".
  • Read the terminals: top 1/3/5 (or L1/L2/L3) is line-in, bottom 2/4/6 (T1/T2/T3) is load-out; coil A1/A2 (A2 often has two holes for easy wiring); aux 13-14 is NO, 21-22 is NC.
  • Arc chute: the plastic lamellae above the main contacts; do not run energized with it removed.
04

Use cases: what NO and NC each handle

Once you grasp the "de-energized state" rule, the scenarios fall into place:

ScenarioContacts usedLogic
Jogging (machine tools, cranes, electric valves)Main (NO) + Start button (NO)Runs only while held, stops on release; no self-hold
Continuous self-holding (pumps, fans, conveyors)Main (NO) + auxiliary NO for seal-inAfter start, its own NO keeps the coil energized
Stop / E-stopStop button (NC)Default conducting; press to open the coil; de-energized = safe
Reversing interlock (hoists, feeds)The other contactor's NC in series with this coilOne pulls in and cuts the other, preventing phase short
Star-delta reduced-voltage startMain (NO) ×2–3 + NC interlock + timerStart in star (reduced V), switch to delta after delay
Fault alarm / safety interlockNC as monitoring contactOn abnormal de-energize, NC resets closed and triggers alarm
Run indicator / PLC feedbackAuxiliary NOAfter pull-in, NO closes and lights the indicator or feeds the PLC
Design principleAny logic that "must act on de-energization to ensure safety" (stop, interlock, protection, alarm) uses NC; any logic that "acts only on energization to execute a command" (start, self-hold, feedback) uses NO. This also follows the Fail-Safe philosophy: when control power drops, the NC contact returns to closed and the system enters a safe state.
05

How to wire (main + control circuits)

① Main circuit: the path of three-phase power

The main circuit carries only large current, and the order must not be reversed (line-in at the bottom, load-out at the top would leave the top live when open — dangerous for maintenance).

L1 L2 L3 QF Breaker KM Main 1-2·3-4·5-6 FR O/L relay M Motor
Main circuit: 3-phase supply → breaker QF → contactor main contacts KM → thermal overload relay FR → motor M.

② Control circuit: self-holding (start-hold-stop) circuit

Example with 220 V control (if using 380 V control, connect A2 to another phase instead of neutral). This is the most classic contactor logic — master it:

L N FU SB1 Stop (NC) SB2 Start (NO) KM 13-14 hold (NO) KM coil SB2 and KM 13-14 are in parallel: after release, the holding contact keeps the coil energized
Self-hold: L → FU → SB1 (NC) → [SB2 (NO) ∥ KM 13-14 (NO)] → KM coil → N.
  1. Press SB2 (Start, NO): the control loop closes, KM coil energizes, main contacts close → motor runs; meanwhile the auxiliary NO 13-14 closes.
  2. Release SB2: current reroutes through the now-closed KM 13-14 and the coil stays energized — this is "self-holding" (seal-in).
  3. Press SB1 (Stop, NC): the loop is cut, KM releases, main contacts and 13-14 open together, motor stops.
  4. Thermal relay FR trips: its NC contact (95-96) should be in series in the control loop, opening the coil on overload → protection.

③ Jogging circuit

Simply remove the KM 13-14 holding branch from the diagram above (do not parallel the self-hold contact): hold SB to run, release to stop. Common for machine-tool positioning, crane jogging, and valve fine adjustment.

④ Reversing interlock (the most critical safety measure)

Forward/reverse uses two contactors KM1 (FWD) and KM2 (REV) to swap two phase sequences. If both pull in at once, it causes a phase-to-phase short, so interlock is mandatory:

L N SB1 Stop (NC) SB2 FWD (NO) KM2 21-22 (NC) KM1 coil KM1 13-14 (NO) SB3 REV (NO) KM1 21-22 (NC) KM2 coil KM2 13-14 (NO) KM1's NC (21-22) is in series with KM2's coil, and KM2's NC with KM1's — one pulls in and locks out the other (electrical interlock)
Reversing interlock: each coil loop carries the other's NC contact in series, plus self-hold; in practice also add a mechanical interlock module (LA9).
High-voltage warningReversing control must have double interlock: ① electrical interlock (as shown, the other's NC in series); ② button interlock (compound buttons that break the opposite loop when pressed); ③ a mechanical interlock module. Using only one risks a short-circuit from contact welding.

⑤ Star-delta reduced-voltage start (brief)

Large motors (generally >15 kW) draw 6–7× rated current on direct start, so star-delta is used: three contactors KM1 (main), KM△ (delta), KMY (star) plus a timer KT. KMY and KM△ also use an NC interlock; KT delays the switch from star to delta. The wiring logic is the same as above — just more main-contact combinations; design it against the specific motor nameplate.

▶ Golden wiring notes

  • Coil voltage must match the nameplate: a 220 V coil on 380 V burns instantly; a 380 V coil on 220 V won't pull in. This is the most frequent field fault.
  • Main contact in/out order: line-in on top, load-out on bottom (L1/L2/L3 up, T1/T2/T3 down) so the lower side is dead when open.
  • Aux contacts only in the control circuit: tiny capacity — never carry the main load or a high-power indicator.
  • Refit the arc chute: the main-contact arc lamellae decide breaking capacity; missing them causes arcing and burnt contacts.
  • Inductive-load protection: across a DC coil or long control wire, add an RC snubber / varistor / flyback diode to suppress switching spikes and extend contact life.
  • De-energize and verify before work: all wiring and maintenance must be done after power-off and verified dead (licensed electrician).
06

Selection cheat-sheet & troubleshooting

Four-step selection mnemonic

① Match power to ratingMotor power → current rating (see cheat-sheet above)
② Copy the coilRead the old unit's side nameplate coil code (M7/Q7/BD…)
③ Add contactsAux insufficient → LA1DN module; interlock needs a separate mechanical interlock
④ Step down oneFrequent/heavy/hot duty → step current down one notch

Common fault quick-reference

SymptomPossible causeTroubleshoot
Coil buzzing / won't pull inControl voltage too low; iron-core face dirty or rustedMeasure A1-A2 voltage ≥85% rated; clean the core face
Coil burnedVoltage mismatch (too high/low long-term); frequent operationVerify nameplate coil code; confirm control supply
Contacts welded, won't releaseBreaking current too high; arc chute missing; AC-4 overloadRe-select by AC-3/AC-4; refit the arc chute
Motor won't run but coil pulls inMain contact in/out reversed; a phase loose (single-phasing)Check 1-2/3-4/5-6 wiring and tightening torque
Self-hold failsAux NO (13-14) not paralleled or poor contactMultimeter: check 13-14 closes with pull-in
Both FWD/REV pull inInterlock NC welded or not wiredCheck KM1/KM2 21-22 and the mechanical interlock
07

FAQ

Is the LC1 "closed" the NC? How do I tell NO from NC at a glance?
Yes — the electrician's "closed contact" is NC (Normally Closed). The most direct method: with the coil de-energized, use a multimeter buzzer on the auxiliary contacts — beeping means NC, silent means NO. The terminal number also works: ending in 1-2 is NC, ending in 3-4 is NO.
Is the "10" in LC1D0910 1-open or 1-closed?
This is legacy numbering: in old models 10 = 1 NO and 01 = 1 NC. Current 3-pole LC1D already builds in 1NO + 1NC; newer numbers (e.g., LC1D09M7C) often omit this segment. So don't overthink "0910" — it still comes with one NO and one NC auxiliary contact.
Can the domestic CJX2 replace LC1D?
Dimensions and mounting (35 mm rail) are basically compatible; CJX2-0910 corresponds to LC1D0910 with the same pinout, so it can substitute. But for applications where quality, life, and certification matter, prefer the original Schneider.
Coil 220 V or 380 V?
It depends on the control supply. Most domestic equipment control is 220 V (line + neutral) → M7; if control is taken from two mains phases at 380 V → Q7; PLC/safety loops are often 24 V → BD. Always follow the old unit's nameplate.
Why is the stop button NC and the start button NO?
This is the Fail-Safe principle: the stop button is normally conducting, so if control power drops or the button wire falls off, the motor stops immediately — it won't "fail to stop". The start is NO, so de-energized defaults to not starting, which matches safe habits.